Guide for Victorian workplaces
Test and tag requirements in Victoria
Test and tag requirements in Victoria come from the employer's general duty under the Occupational Health and Safety Act 2004 to keep plant and the workplace safe, not from a regulation that names test and tag. This guide, one of our facilities and compliance guides, explains what that duty means in practice and how often each type of workplace should test.
It is written for business owners, office and facility managers, and strata managers who want to know what is law, what is the standard, and what is good practice.
Is test and tag a legal requirement in Victoria?
Not by name, but in practice most workplaces need it. Section 21 of the Occupational Health and Safety Act 2004 requires an employer to provide and maintain plant and systems of work that are safe, so far as is reasonably practicable. Portable electrical equipment is plant.
WorkSafe Victoria's electrical safety guidance says those systems of work should cover the inspection, testing and maintenance of electrical equipment, and it refers employers to AS/NZS 3760:2022 for recommended intervals. Testing and tagging to that standard is the usual way a business shows it has met the duty.
Interval table
Test and tag intervals by workplace type
AS/NZS 3760 sets intervals by the environment equipment is used in, from three months on building sites to up to five years in low-risk areas. The table lists the maximum intervals in the standard; a risk assessment for your workplace can set shorter ones, never longer.
| Environment | Inspect, test and tag at least every | Examples |
|---|---|---|
| Construction and demolition | 3 months | Building sites, site sheds, tools used on renovation work (AS/NZS 3012 also applies) |
| Hire equipment | 3 months, plus a check before every hire | Tools, generators and event lighting rented out |
| Factories, warehouses and production | 6 months | Power tools, battery chargers, fans and leads on a factory floor |
| Commercial cleaning equipment | 6 months | Vacuums, scrubbers, polishers and carpet machines |
| Hostile environments, or equipment flexed or open to damage | 12 months | Commercial kitchens, workshops, gyms, outdoor areas |
| Residential areas of hotels, motels and hostels | 2 years | Kettles, hair dryers and lamps in guest rooms |
| Not flexed, not open to damage, not hostile | Up to 5 years | Desktop computers and monitors in an office |
Intervals summarise AS/NZS 3760:2022. Buy the full standard from Standards Australia if you are writing a formal testing procedure.
By workplace
What test and tag looks like in each type of workplace
The same standard plays out very differently in an office and on a factory floor. Pick your workplace to see the usual interval, what gets tagged and what tends to be missed.
Offices and professional suites
Most office equipment sits still on a desk, so the standard allows long intervals for it. Kitchen appliances, heaters and anything moved around the floor are treated differently.
- Computers and monitors: up to five years if not moved or open to damage
- Kettles, toasters and microwaves: usually twelve months
- Portable heaters and fans brought from home
- Extension leads and power boards under desks
- Daisy-chained power boards removed, not tagged
- Full retest after an office move or fit-out
Warehouses, factories and workshops
Six months is the interval for factories and warehouses, and it applies to most items that plug in on the floor.
- Power tools and drop leads
- Battery chargers for forklifts and scanners
- Pedestal fans and portable lighting
- Leads that run across forklift aisles
- Welders and compressors with flexible cords
- Pre-use visual checks between test dates
Commercial kitchens and hospitality
Heat, water, grease and constant movement make kitchens a hostile environment, so twelve months is the usual starting point and many venues choose shorter.
- Mixers, slicers and stick blenders
- Bain-maries, warmers and toasters
- Plug-in fridges and display cabinets
- Cords checked for heat damage and cracking
- RCD protection on kitchen circuits
- Glasswashers and coffee machines with plugs
Construction and demolition sites
Construction is the one place where Victoria has specific guidance: WorkSafe's industry standard for electrical installations on construction sites, read with AS/NZS 3012.
- Testing generally every three months
- Colour-coded tags that change each quarter
- Site switchboards and builders' leads
- Portable RCDs on every lead
- Equipment from home not used on site untested
- Separate records kept for the principal contractor
Strata and owners corporation common property
An owners corporation that employs staff or engages contractors to use its equipment has duties for that equipment too, even though no one works there full time.
- Cleaning machines kept in common storerooms
- Gym equipment on common property
- Appliances in shared lounges and rooftop kitchens
- Pool pumps with plug-in connections
- Contractors' own tools: ask for their register
- Records kept with the committee's documents
In detail
The rules behind test and tag, one at a time
Each of the questions below comes up whenever a business sets up a testing routine. Open one to read the detail, including where the rules in Victoria differ from what you may read for other states.
Why NSW and Queensland test and tag laws do not apply here
Most states and territories have adopted the national model work health and safety laws. Their regulations name inspection and testing for electrical equipment used in hostile conditions, such as moisture, heat, vibration or dust. Victoria has not adopted those laws and still runs under its own OHS Act, so articles that quote that regulation are describing another state.
Do you need a test and tag licence in Victoria?
There is no separate test and tag licence in Victoria. AS/NZS 3760 and WorkSafe Victoria talk about a competent person, which can be a licensed electrician or someone trained to do pass or fail testing with the right instrument.
The difference matters when an item fails. A person trained only in testing can tag it out of service, but repairs to electrical equipment must be done by a licensed electrician or other competent repairer.
RCD testing requirements in Victoria
RCDs, or safety switches, are tested two ways: a push-button test by the user, and an operating time test with an instrument. WorkSafe Victoria's guidance lists a push-button test as often as daily for portable RCDs in high-risk areas and every six months for fixed RCDs.
It lists the operating time test every twelve months in high and medium risk areas and every two years in low-risk areas. Results should be recorded alongside the appliance register.
New equipment
Under AS/NZS 3760, brand-new equipment does not need an electrical test before it is first used. It should still be checked for damage and either tagged or recorded as new to service, with its first test due at the normal interval for the area it works in.
Test and tag colours
Outside construction, AS/NZS 3760 does not require a colour; the tag must show who tested the item and when, and when the next test is due. On construction sites a quarterly colour code is used so an out-of-date tag stands out at a glance:
- Red: December, January, February
- Green: March, April, May
- Blue: June, July, August
- Yellow: September, October, November
Records to keep
Start with a register that lists each item, where it is, the result of each test, who tested it and when the next test is due. Record failed items too, with what was done: repaired, replaced or thrown out. An inspector, insurer or principal contractor will usually ask for the register before looking at any tags.
Downloads
Printable test and tag checklist and register
Three printable documents to use alongside this guide. They will be added here as downloads once a licensed electrician has checked them.
- Interval table to printThe intervals by environment on one A4 page for the staff room or workshop wall.
- Test and tag register templateA spreadsheet with columns for item, location, result, tester and next test date.
- Pre-use visual check card
Test and tag questions from Victorian workplaces
Does an office in Victoria legally have to test and tag?
There is no regulation that names it, but an office employer must keep its electrical equipment safe under the OHS Act 2004. Testing to AS/NZS 3760 is how most offices show they have done that, and low-risk desktop equipment can go up to five years between tests.
What can WorkSafe do about unsafe electrical equipment?
WorkSafe enforces the general duty. An inspector who finds damaged or unmaintained electrical equipment can issue an improvement or prohibition notice, and serious breaches of the OHS Act can be prosecuted.
Who is allowed to test and tag in Victoria?
A competent person: a licensed electrician, or someone trained to use a portable appliance tester and pass or fail equipment. Only a licensed electrician or other competent repairer should repair an item that fails.
What do the colours on test tags mean?
On construction sites the colour shows the quarter the item was tested in: red for summer, green for autumn, blue for winter and yellow for spring. Elsewhere the colour has no set meaning; the dates written on the tag are what count.
How often should RCDs be tested?
WorkSafe Victoria's guidance gives a push-button test as often as daily for portable RCDs in high-risk areas, six-monthly for fixed RCDs, and an operating time test every one or two years depending on the risk of the area.
Have the testing done for you
Golden Star books licensed electricians to test, tag and keep the register for offices, warehouses, kitchens and strata buildings across Melbourne.