Corridor with timber floor and wall panels, the kind of exit path checked during emergency lighting testing

Essential safety measure

Emergency and exit lighting testing

Emergency lighting testing proves that every emergency light and exit sign in a building stays lit on battery power for its rated time when the mains fails. Golden Star books the six-monthly test to AS/NZS 2293.2 through its commercial electrical team and records every fitting in a logbook.

That logbook is what the owner relies on for the annual essential safety measures report, so it is kept up to date after each visit and after each repair.

Each test is run by a licensed electrician from the contractor we engage

Scope

What each emergency lighting test includes

A six-monthly visit checks that each fitting can be seen, switches over to battery and lasts the full test, then records the result. These are the six parts of the visit.

  • Fitting registerEach emergency light and exit sign is numbered and matched to the floor plan, so a failure can be found again quickly.
  • Visual checkLenses, diffusers and exit sign faces are checked for damage, and the charge indicator is checked on every fitting.
  • Discharge testMains supply to the lights is isolated and each fitting must stay lit on battery for its full rated time, usually 90 minutes.
  • Visibility after fit-outsExit signs hidden by new partitions, shelving or signage are reported, because a sign nobody can see does not do its job.
  • Fault listEach failure is listed with its location and the likely cause: battery, lamp, charger or the whole fitting.
  • Logbook entryResults are written into the logbook kept on site and the date of the next test is set.

Intervals

When emergency and exit lights are checked

AS/NZS 2293.2 sets a six-monthly routine for testing emergency lighting, and the rest of the year is about catching failures between tests. This is how the cycle runs for a typical building.

Every six months

  • Discharge test of every fitting on battery
  • Visual check and logbook entry

After a failed test

  • Battery, lamp or fitting replaced
  • Retest of the repaired fitting and a new logbook line

Between tests

  • Staff or the building manager report a dark sign or a red charge light
  • A request in GS Connect sends an electrician out

Once a year

  • Owner uses the logbook for the annual essential safety measures report
  • Fittings that keep failing are listed for replacement

Emergency lighting is one of the essential safety measures Victorian owners must keep in working order. See essential safety measures for the full list and the annual report.

Who it is for

Buildings that need exit light testing

Most commercial and public buildings in Victoria have emergency lighting and exit signs installed under their building permit. These are the sites where we book exit light testing most often.

Apartment and strata buildings

Stairwells, corridors and car parks on common property. The owners corporation pays and the strata manager usually holds the logbook.

Office buildings

Each floor plus fire stairs. Tests are timed so a floor is not left with flat batteries just before evening use.

Shops and shopping centres

Back-of-house corridors and loading docks, where stock stacked in front of exit signs is the most common defect.

Warehouses and factories

High-bay fittings that need a lift to reach, so access is planned and priced before the visit.

Schools and childcare

Tested during holidays or after hours so classrooms are not disrupted by the isolation.

Medical and aged care

Occupied around the clock, so fittings are tested in small groups and never a whole wing at once.

On the day

How an emergency light test visit runs

A test visit takes a few hours for a small building and longer for a large one, because every fitting must run on battery for the full test time. The steps below are the same for every site.

  1. 1

    Count and plan

    We ask for the number of fittings and the floor plan or old logbook, then book a time that suits the building.

  2. 2

    Warn occupants

    Tenants are told the lights will be on battery during the test. In aged care and medical sites the test runs in sections.

  3. 3

    Run the discharge test

    The electrician isolates the lighting circuits, times each fitting on battery and notes any that dim or go out early.

  4. 4

    Restore and recharge

    Mains supply is restored. Batteries need hours to recharge after a full discharge, which is why tests are not booked just before a busy night.

  5. 5

    Report and repair

    You receive the fault list with prices. Approved repairs are done and retested, and the logbook is updated.

White reception area with a polished dark floor, a common area where emergency lights are tested

Rules that apply

Standards and records for emergency lighting testing

Emergency lighting is designed to AS/NZS 2293.1, tested to AS/NZS 2293.2, and maintained by the owner under the Building Regulations 2018. Insurance certificates for the electricians we engage are on our accreditations and safety page.

Standards and records for emergency lighting testing
ItemWhat appliesGolden Star detail
Routine testingAS/NZS 2293.2, six-monthlyBooked and tracked in GS Connect
Design and durationAS/NZS 2293.1 and the National Construction CodeRated duration checked against the fitting label
Owner's dutyBuilding Regulations 2018 (Vic), essential safety measuresLogbook supplied for the annual report
Who testsLicensed electricianAvailable on request
InsurancePublic liabilityAvailable on request

Price guide

Emergency lighting testing prices

Testing is priced per fitting, and repairs are priced on top once we know what failed. The biggest saving is usually replacing only the failed battery or lamp instead of the whole fitting, so our fault list says which part failed.

Emergency lighting testing prices
ItemFromWhat changes the price
Six-monthly testOn quoteNumber of fittings and how spread out they are
Battery replacementOn quoteBattery type and whether the fitting has a drawer or must be opened
Fitting replacementOn quoteOld fittings with no spare parts, or a switch to LED
Minimum visitOn quoteSmall buildings with only a few fittings

Emergency light testing across Melbourne

We book emergency light testing for buildings across metropolitan Melbourne. Apartment towers in Southbank and Docklands are tested in sections, floor by floor, while single-level shops and warehouses in the south-east are often done in one visit. See the list of areas we service.

Regions of Melbourne covered by Golden Star Port Phillip CBDInner southInner eastBaysideSouth-eastOuter south-eastWestNorth and eastSchematic, not to scale

Emergency lighting testing questions

Ask us about your own building at info@goldenstar.au.

How much does emergency and exit light testing cost in Melbourne?

It is charged per fitting tested, with a minimum for small buildings, and any repairs are quoted separately. Send us the number of fittings, or an old logbook, and we will give you a fixed price.

How often do emergency and exit lights need testing?

Every six months under AS/NZS 2293.2, with a discharge test on battery each time. Failed fittings should be repaired and retested promptly rather than waiting for the next round, and the results recorded in the logbook.

Do small buildings need the full 90-minute test?

Emergency lights are tested for the duration they were designed for, which is 90 minutes for most Australian buildings. A small block is not exempt because it is small; if the fittings are installed under the building permit, they must be maintained and tested.

Are the electricians who test the lights insured and inducted?

Yes. The electricians hold Victorian licences, work for the registered contractor we use, and complete your site induction before the first test.

Can exit light testing be done after hours?

Yes, and for busy offices and shops it often is. Keep in mind that batteries need several hours to recharge after the test.

Which areas of Melbourne do you test in?

We test across metropolitan Melbourne. Regional Victorian buildings are taken on case by case, depending on how many fittings there are and our booking load.

Book your next emergency light test